Operator control panel OP2
Hardware - SIMADYN D
10-3
Edition 03.2001
10
10.2 Process data handling
Process data handling is selected using the VAL key. The LED in the key is
lit if process data handling has been selected (the VAL key).
10.2.1 General
information
Two of a total of 24 process data can be simultaneously displayed (upper
and lower display line). The 24 values are sub-divided into two panels
(V1..V12 + SHIFT) for easier selection.
The sub-division of the two panels according to setpoints and actual values
can be configured as required (for instance, 20 actual values can be
configured or just 3). The sub-division according to setpoints and actual
values is exclusively configured in SIMADYN D.
The selected process data values are always displayed normalized, in
accordance with the pre-setting (default) together with dimension and name.
If a name has not been configured, then the „VALUE xy“ (xy = 1 ..24)
designator is displayed as default value.
If a non-configured process data is selected, then operating message No. 14
(„
NO MEASURED VALUE INITIALIZED
“) is displayed. This text is displayed
for 3 seconds, and then the previous value is re-displayed.
ACCESS
VALUE 24
=
=
-0.123456789012345 Rev/min
-17.365195745 E-55 POUNDS
Designator
Value
Dimensions
% data
10.2.2
Behavior at run-up
The OP2 automatically goes into the process data handling mode after it has
been initialized. The last selected values are displayed again. At first run-up,
the first two configured values are displayed (normally V1 and V2). If only
one process data has been configured, then operating message No. 14 is
displayed in the lower display line („
NO MEASURED VALUE INITIALIZED
“).
If no process data have been configured at the SIMADYN D side, the OP2
goes into the basic message system processing function. If process data
handling is selected at a later time, then operating message No. 14 is
displayed in the upper line („
NO MEASURED VALUE INITIALIZED
“). The
text is displayed until another basic function is selected.