Program memory modules / Interface modules
8-26
Hardware - SIMADYN D
Edition 04.2011
8.6.3 Technical data
Mounting system
Housing for snapping onto mounting
rails
Dimensions (W x H x D)
45 x 129 x 160 mm
Weight
Approx. 0.32 kg
ambient temperature for approbations
max. 50
°
C
SIMADYN
D
Plant/system
side 24 V DC
Plant/system side
48 V DC
Power supply
voltage (V
V
)
24 V DC
24 V DC
48 V DC
Permissible range
20 to 30 V DC
20 to 30 V DC
40 to 60 V DC
Briefly t<500 ms
1.5 x V
rated
1.5 x V
rated
1.5 x V
rated
Current drain at the
nominal value
90 mA
50 mA
50 mA
The maximun current on connector X3 is 1 A, if this is the power supply
for several interface modules. The maximun current on connector X4 is
2 A, if this is the power supply for several interface modules.
Plant/system
side 24 V DC
Plant/system
side 48 V DC
No.
8
8
Input voltage for
‘1 signal’
13 to 30 V DC
26 to 60 V DC
‘0 signal’
-3 to +6 V
1)
-3 to +12 V
1)
Input current (‘1signal’)
6 mA
6 mA
1)
Or open-circuit input
General data
ambient
temperature
Power supply
Binary inputs
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China