12 Monitored lines
– not monitored for faults or tripping
•
MS8SE (control element) can be operated in operating mode 1 (permanent 1:1 assign-
ment) and inoperating mode 2 (system-wide control)
•
Only 3 parallel displays can be simultaneously activated on an MPL(reason: max. cur-
rent load of an MPL = 24 mA, 1 activated control unit requires approx. 4 mA,control
units and control elements are activated in the same cycle)
•
Fault
detection
– all pulse-polling detector elements (including control elements) can cause a fault
•
Alarm buffering (ALZ) for Master20 and ABM
•
Event delay for BR800, BR81, BR82 and MS8EB
•
No fault delay
•
Detector zone formation
– every detector in an MPL can be assigned one detector
– cross-module formation not possible
•
Detector zone functions (as in SIGMASYS)
– 2-MG
dependency
– – 2-detector dependency
– – ALORG (alarm organisation)
•
Alarm zone formation
– cross-module formation possible
– – mixing with MPC and GMG detector zones possible
•
Operating inputs (e.g. via receiver module MS8EB)
•
Maximal line data 300
Ω
, 250 nF
12.2.1 Differences vis-à-vis AMP (SM88) or PMG (BMS) Vis-à-vis AMP
•
no special AMP functions (suction systems, sterile areas)
•
no different sensitivities (+, –).
Pulse-polling
detector element
Evaluation procedure ( code )
Remark
- BR800
Standard (0)
smoke detector
- BR81
Standard
(0)
opt. smoke detector
- BR82
Standard
(9)
1blank value m (0)
EMV
(9)
opt. smoke detector
FDOOT241-8
Standard (0)
neural fire detector
- BD857
Standard
(5)
heat detector
- RSG8
Standard
(5)
closed-circuit current alarm device
- DR8
Standard
(5)
manual call point
- DR8AU
Standard
(1)
manual call point with autom. inspection
- SDR8
Standard
(5)
manual call point
-SDR8AU
Standard
(1)
manual call point with autom. inspection
- MS8EB
Standard
(3)
receiver module
- ABM
Standard
(B)
addressing module
80 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Содержание SIGMASYS C
Страница 4: ......
Страница 30: ......
Страница 38: ......
Страница 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 48: ......
Страница 62: ......
Страница 84: ......
Страница 110: ......
Страница 120: ...15 Project planning examples 112 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 130: ......
Страница 132: ......
Страница 134: ......
Страница 137: ......