8 Transponders and loop elements
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
49 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
A freely programmable 16-character text is displayed in the second line.
witch is available to enable operation by authorised persons. Four free keys
individually programmed as operating inputs.
els can be installed per MPC module.
indicating panel.
A key-operated s
can be used and
Eight zone operating pan
32 zone operating panels can be installed per SIGMASYS M control and
8.3
Outputs
8.3.1
Indicator panel control facility SPF 3200
64 freely programmable outputs for controlling site plan indicator panels or non-monitored un-
cilities.
critical control fa
N.B.:
short-term by a restart or EMC influences. Con-
sequently, these outputs should only be used for uncritical control facilities. Output current per
uired when connecting LEDs to the indicator panel control facility.
Bright LEDs with a power consumption of between 5 and 10 mA should preferably be used.
”
e address on the loop. The indicator panel con-
tor panel control facility requires a power supply unit
Indicator panel outputs can be deleted in the
output is approx. 8 mA.
No series resistor is req
Two entries are available in SPF 3200 for disabling the acoustic signal and for the “Lamp test
function.
The indicator panel control facility occupies on
trol facility is supplied as a PCB for installation in boards or housing to be installed on the
building side.
A metallic housing should be used to avoid unwanted interference.
The indica
Connection
A maximum of 6 connection cables are available for each of the ten (eleven) LED connec-
1500 mm in length and post
connector at one end.
rol modules each with 11 C97117-Z3004-C1 relays can be connected to the in-
ys each with 2 potential-free changeovers
tions for the indicator panel control facility.
Ten-LED connection line C24217-A26-B2 as standard flat cable
Six Opto cont
dicator panel control module.
Opto control module:
11 rela
Maximum contact load:
3 A / 250 VAC, 5A / 30 VDC, 100 V/0, 5 A/10 W
Programmable control pattern:
static or flashing 1 s
8.3.2
Control module SPF 5100
The control module SPF 5100 is connected to the detector outputs of the automatic
US, E
ax. line length from detector to the
A floating changeover contact is provided on the output side. Rating 30 V / 1 A.
The control module does not occupy an address on the loop and also supports cross-loop
programming.
SIGMASYS detector (BASE, PL
XPERT, COMBO) (m
control module: 10 m).
Содержание SIGMASYS C
Страница 4: ......
Страница 30: ......
Страница 38: ......
Страница 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 48: ......
Страница 62: ......
Страница 84: ......
Страница 110: ......
Страница 120: ...15 Project planning examples 112 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 130: ......
Страница 132: ......
Страница 134: ......
Страница 137: ......