8 Transponders and loop elements
52 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Number of technically addressable components max. 64
Max. permitted line parameters
M
k
ax. permitted line capacity (primary and secondary spurs) 200nF, corresponds to approx. 2
m of the standard cable quality IY (ST) Y 0.8 mm.
Max. permitted line resistance 150 ohm (all spurs together).
8.4
, current, dimension
Technical data, voltage
s
U
min
U
max
I
Ruhe
I
max
Output
Input idle /
alarm
Dimensions
(in mm)/
Installation
Loop
add.
Maxitransponder
SPF3500 / 4STE
4 inputs/outputs
22V
28V
25mA
+10mA
per
MS6/7
210mA
126mA per
output
max. 210mA
permitted
Max 140
Ω
line resistance.
per GMG MPL
130x130x75 /
on
option slot
4
Minitransponder
SPI3400
2 inputs/outputs
18V
28V
18mA
53mA
1. Open Col-
lector 10mA
2. 12V/25 mA
2 Lines 6.8k
Ω
,
monitored on
±40%
line < 600
Ω
54x31x22
15 mm
top-hat rail
AP 21 – 225
1
Contact coupler
SPF5300
4 inputs
-
-
-
-
-
3,3k
Ω
/560
Ω
20x64x28
15 mm
top-hat rail
AP 21 – 225
1
Multiple control fa-
cility
SPF5200
8 outputs
12V
28V
1mA
100mA
Relay contact
rating up to
30V
15mA-1A
-
117x117x20
on
option slot
1
Indicator panel
control facility
SPF3200
64 outputs
12V
28V
2mA
200mA
8mA für LED
without series
resistor
-
160x100x40
installed in
steel housing
1
Opto control mod-
ule 11 Relays for
indicator panel
control facility
20V
28V
-
35mA
je
Relais
Relay contact
rating up to
5A 30V DC
3A 250V AC
per opto coupler
3 mA
B x H x T
180x78x52
-
Control module
SPF5100
12V
28V
-
22mA
Relay contact
rating up to
30V
15mA-1A
-
50x45x18
in distribution
cabinett
-
Zone operating
panel
SPF 3300
12V
28 V
15 mA
210mA
150mA
Display
2x 16
4 function keys
208x158x35
incl. housing
1
SIGMALOOP split-
ter
-
-
-
-
4 spurs
1 spur
115x90x25
top-hat rail in-
stallation
Table 20: Technical data, voltage, current dimensions
Содержание SIGMASYS C
Страница 4: ......
Страница 30: ......
Страница 38: ......
Страница 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 48: ......
Страница 62: ......
Страница 84: ......
Страница 110: ......
Страница 120: ...15 Project planning examples 112 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 130: ......
Страница 132: ......
Страница 134: ......
Страница 137: ......