Appendix
A.8 Technical specifications
SICHARGE Operating Manual ERK
Operating Manual, 02/2022, A5E48572458-AD
55
Available continuous power
If both charging points are used for a longer time period (> 2 h), the max. total power or the
max. total current must be reduced by 10% for each external conductor (to 56.7 A/39.1 kW).
Storage and transport
Follow the following framework conditions when storing and transporting the charging
station:
•
Protect packaged goods from precipitation and moisture. The transport packaging is not
suitable for outdoor exposure.
•
The permissible storage temperature of the charging station is -25 to +50 °C.
•
The permissible air humidity is 5 to 95%, non-condensing.
•
The charging station may only be transported in the transport packaging provided for this
purpose using the supplied safety and shock-absorbing materials.
•
To transport the charging station, disconnect all external cable connections.
Set switches of the fuses to the "Off" position.
Close any transport locks on the cover.
•
Avoid shocks and impacts during transport.