40
Overhaul
The adjustment requires the insulating pushrod length
be varied by turning the threaded pushrod end into or
out of the pin coupling the pushrod to the breaker jack
shaft.
Required trunnion center below bell crank shaft center:
VS12015
3mm
(0.118 in)
VS25002
4mm
(0.157 in)
VS17006
4mm
(0.157 in)
VS10006
5.5mm (0.217 in)
VS10028
4mm
(0.157 in)
VS15050
4.5mm (0.177 in)
Engage pushrod to bell cranks and gage trunnion shaft
center distance below bell crank shaft center. If less
than required, the pushrod must be shortened,
screwed into the jackshaft pin. If greater than required,
the pushrod must be lengthened by screwing it out of
the jackshaft pin.
By interactively engaging the trunnion shaft center.
disconnecting the coupler, adjusting the coupler, reat-
taching the coupler to the bell cranks, and again
gaging the trunnion center, the required trunnion
center position relative to the bell crank shaft center
will be achieved.
The gage block (18-750-171-001, -002, -003, or -004
as appropriate), when held firmly on the trunnion, will
just contact the lower surface of the bell crank shaft at
the correct open position (
Figure 52
).
17. Concluding Operations
17.1. Torque vacuum interrupter stationary and movable
contact fasteners to values indicated in
Table 7
.
17.2. Using procedure shown in
Figure 51
and torque
limits established in
Table 7
secure interrupter clamp
hardware.
17.3. For 2000A ratings using VS15050 interrupter, and all
3000A ratings not using the chair support design.
After the hardware for the flexible shunt (interrupter)
clamp have been secured in section 17.2, the heat
sinks that were removed in section 5 must be replaced.
The heat sinks must be installed with a coating of
copper-loaded grease (T&B “Kopr-Shield”),
approximately 1/10 inch thick, between the heat sink
and the flexible shunt clamp.
17.4. Replace all barriers. Special attention should be
given to assure that all barriers and supports are
mounted in exactly the same configuration as they
N
No
otte
e:: C
Ch
he
ecck
k tto
o b
be
e cce
errtta
aiin
n tth
he
e iin
ntte
errrru
up
ptte
err cclla
am
mp
p h
ha
ass b
be
ee
en
n rra
aiisse
ed
d iin
ntto
o ffiirrm
m
b
be
ea
arriin
ng
g a
ag
ga
aiin
nsstt tth
he
e m
mo
ov
va
ab
blle
e sstte
em
m sstte
ep
p o
orr rre
etta
aiin
niin
ng
g rriin
ng
g b
be
effo
orre
e sse
eccu
urriin
ng
g
tth
he
e cclla
am
mp
p..
were prior to disassembly. Refer to the notes and
photos taken during disassembly, section 2.
17.5. Perform High Potential Test across open vacuum
interrupter and from each primary extension to ground
(see
Table 3
on page 30).
Figure 46:
GMI Circuit Breaker Side Elevation (Typical)
Figure 47:
VS10006 and VS10028 1200A.