
Startup
7.3 Parameterizing the device
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
93
7.3.4.4
Setting the voltage input
The factory setting for the measuring reference voltage is 400 V. At initial startup, the
following steps must be carried out if the available measuring voltage deviates from this.
Procedure
1.
In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2.
In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
3.
Go to the "VOLTAGE INPUTS" device setting:
<F2>
or <F3>
Figure 7-7
"VOLTAGE INPUTS" device setting
4.
Open edit mode of the "VOLTAGE INPUTS" device setting:
<F4>
5.
Set the desired value:
<F2>
and <F3>
6.
Accept the value:
<F4>
The value of the voltage input is permanently saved and becomes effective immediately.
The display returns to display mode.
7.
Return to one of the selection menus or to the measured values display:
<F1>
Содержание SENTRON PAC4200
Страница 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Страница 84: ...Connecting 6 5 Grounding of the Ethernet cable SENTRON PAC4200 84 Manual 09 2008 A5E02316180B 01 ...
Страница 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Страница 146: ...Parameterizing 9 2 Parameterizing the operator interface SENTRON PAC4200 146 Manual 09 2008 A5E02316180B 01 ...
Страница 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Страница 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Страница 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...