Technical data
11.1 Technical data
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
161
Degree of protection and safety class
Protection Class
II
Degree of protection according to IEC 60529
Device front
IP65
Type 5 enclosure acc. to UL50
Device rear
Device with screw terminal
IP20
Device with ring lug terminal
IP10
If higher degree of protection requirements are placed on the application engineering, the
customer must take suitable measures
Environmental conditions
Temperature range
Ambient temperature during operation
- 10 °C to + 55 °C
Ambient temperature during transport
and storage
- 25 °C to + 70 °C
Relative humidity
95% at 25°C without condensation (normal
conditions)
Site altitude above sea level
max. 2000 m
Degree of pollution
2
Environmental tests
In accordance with IEC 60068
Содержание SENTRON PAC4200
Страница 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Страница 84: ...Connecting 6 5 Grounding of the Ethernet cable SENTRON PAC4200 84 Manual 09 2008 A5E02316180B 01 ...
Страница 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Страница 146: ...Parameterizing 9 2 Parameterizing the operator interface SENTRON PAC4200 146 Manual 09 2008 A5E02316180B 01 ...
Страница 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Страница 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Страница 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...