Internal Accessories
Auxiliary Switches
5.)
Secure the trip unit in place with the retaining screw
located at the top of the trip unit. Torque to 6-8 in. lbs. If
trip unit top is not secured properly, the interlock will
prohibit closing of the breaker.
6.)
Replace the front cover of the breaker, being careful not
to pinch wire leads routed to secondary disconnects or
terminal blocks. Secure with eight (8) Phillips head screws.
Installation of the auxiliary switch is complete.
Wiring Information
Содержание SBA 1200
Страница 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Страница 88: ...86 Outline Dimension Drawing 2000A Stationary Drawout Element Courtesy of NationalSwitchgear com ...
Страница 89: ...87 Outline Dimension Drawing 2000A Stationary Drawout Element Courtesy of NationalSwitchgear com ...
Страница 90: ...88 Outline Dimension Drawing 2000A Moveable Drawout Element Courtesy of NationalSwitchgear com ...
Страница 91: ...89 Outline Dimension Drawing 2000A Moveable Drawout Element Courtesy of NationalSwitchgear com ...
Страница 92: ...90 Outline Dimension Drawing 800A Fixed Mounted 1200A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 93: ...91 Outline Dimension Drawing 800A Fixed Mounted 1200A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 100: ...98 Courtesy of NationalSwitchgear com ...
Страница 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Страница 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...