8 0
External Accessories
Enter one of the following letters:
“A”—Phase A or Left Pole
“B”—Phase B or Center Pole
“C”—Phase C or Right Pole
H.
The TS-31 will report the type of test you selected and
give you a chance to abort the test. For example, if “I” was
pressed above. The TS-31 will display:
Instantaneous Test
Press ENTER to Continue or A to Abort.
If you pressed the letter “A” to abort. you will be asked to
enter again
Change: 1 - Test 2 - Catalog 3 - Settings:
I.
Press Enter again to start the test. Press any other key to
STOP the test. Once a test has been started, the TS-31
will respond with:
Trip test. Press Any Key to Abort.
Time Remaining: xx.xxx Sec.
Be careful at this time. Any keypress will abort the test.
J.
The test may take anywhere from a fraction of a second
to minutes to complete, depending on which procedure
was run . If the test passes, the display will show the
following, depending on whether the breaker tripped or
not.
Test Passed. xxx.xx seconds
Press any key to continue.
If the breaker tripped during the test, RESET the circuit
breaker before continuing.
K.
The TS-31 will prompt for the next instructions. The
display will show:
Change: 1 - Test 2 - Catalog 3 - Settings
Enter one of the following numbers:
“1” - select a new test
“2” - enter a new catalog number
“3” - enter a new switch setting
If you enter “1“ you will be sent to step F. Choosing a “2”
will send the program back to step E. Entering “3” which
sends you back to step E, will be slightly different the
second time through. On the second line after the prompt
for the setting, a number or text in brackets will appear.
This will indicate the last setting you entered. If you DON’T
wish to change a setting, just press ENTER . If you DO
wish to change a setting, type in the new setting and
press ENTER.
L.
If you pressed “C” when asked. You will first be prompted
by:
Current Transformer Test
Press ENTER to Continue or A to abort.
Universal Test Kit (TS-31)
and then for the phase to test. A message will then appear
stating the test results. For example:
CT Resistance Test. Phase X PASSED.
Press any key to continue.
M. There are additional ERROR messages which may ap-
pear on the display during this operation which were not
covered previously:
Test Not Running—Check Test Cable.
Press enter to continue.
The test set has sensed that current is not flowing
properly in the breaker under test and that there is either
an open or short circuit between the TS-31 and the
breaker trip unit
Ground Fault is NOT available on a SJD69300.
Press any key to continue.
You will get this error message if you enter a choice that
is not available, such as entering “G” in step F for ground
fault test on a catalog number that does have ground
fault.
Inconclusive Test, Check Settings.
Press any key to continue or A to abort
Note:
This warning will appear if you attempt to run a short
time test with the instantaneous pickup set equal to
or below the short time pickup. It would also appear
if you tried to run a long time test with short time
pickup set to 2. This is only a warning: the test can
still be run. However. passing or failing the test may
not be conclusive.
XX is NOT a Valid Setting.
Press any key to continue.
Note:
This message will appear if you enter a setting value
that does not exist. For example a SMD69700ANGT
has continuous current settings of 20, 30, 40, 50,
60, 70, 80, 90, 100 percent. If you were to enter any
other value than those listed, the above message will
appear.
Test Exceeds Capability of TS-31.
Press any key to continue.
Note:
This message is not likely to occur. If it does, it means
that a test requires more current to run than the TS-
31 can produce.
Unit Too Hot, Please Wait.
Note:
Running many successive high-current long time
tests may over-heat the test set. It will protect itself
from damage by preventing further tests until it has
had a chance to cool down. The display will indicate
when testing can resume.
Содержание SBA 1200
Страница 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Страница 88: ...86 Outline Dimension Drawing 2000A Stationary Drawout Element Courtesy of NationalSwitchgear com ...
Страница 89: ...87 Outline Dimension Drawing 2000A Stationary Drawout Element Courtesy of NationalSwitchgear com ...
Страница 90: ...88 Outline Dimension Drawing 2000A Moveable Drawout Element Courtesy of NationalSwitchgear com ...
Страница 91: ...89 Outline Dimension Drawing 2000A Moveable Drawout Element Courtesy of NationalSwitchgear com ...
Страница 92: ...90 Outline Dimension Drawing 800A Fixed Mounted 1200A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 93: ...91 Outline Dimension Drawing 800A Fixed Mounted 1200A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Страница 100: ...98 Courtesy of NationalSwitchgear com ...
Страница 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Страница 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...