3-36
System Manual
C79000-G8576-C199-06
Where subracks (CC and EU) are arranged one above the other, the
installation clearances in the following table must be observed.
Upper Subrack
Lower Subrack
Min. Clearances
Max. Clearances
S5-135U/ 155U
or
S5-115U
S5-135U
75 mm
87 mm if baffle
is used
The maximum clearance
is limited by the lengths
of connecting cables for
h i
f
d l
or
S5-90U/ 95U/ 100U
S5-115U with fan
60 mm
g
the interface modules.
S5-90U/ 95U/ 100U
S5-115U without fan
100 mm
S5-90U/ 95U/ 100U
75 mm
The following two points should be observed to improve the air circulation
within the cabinet:
The expansion unit with the greatest power dissipation to be removed
should be the upper unit.
If subracks of the S5-135U/155U series are installed together with
subracks of the S5-90U to 115U series in one cabinet, the rear panels of
all subracks must be at the same distance from the rear wall of the
cabinet.
Installation Guidelines
Содержание S5-135U
Страница 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Страница 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Страница 26: ...2 8 SystemManual C79000 G8576 C199 06 Centralized and Distributed Configuration of a Programmable Controller ...
Страница 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Страница 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Страница 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Страница 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...