5-77
System Manual
C79000-G8576-C199-06
QVZ LED
on
During direct access or process image update, a module
addressed by the program no longer acknowledges although
either it has acknowledged in single processor operation
upon reset of the CPU 922 in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide,
CPU 922),
it h
b
t
d i DB 1 ( dd
li t) i
or it has been entered in DB 1 (address list) in
multiprocessor or single-processor operation and has been
recognized as present during the reset.
Possible causes
Module failure.
Module was pulled out during operation, in the stop state
or in the Off state without a subsequent reset.
ADF LED
on
The user program has referenced an I/O address under which
no module is inserted.
ZYK LED
on
The maximum cycle time has been exceeded.
BASP LED
on
Command output is inhibited and the digital outputs will be
directly switched to the safe state.
A detailed description of interrupt and error handling can be found in the
CPU 922 Programming Guide.
LEDs for Fault
Indication and
Signaling
CPUs, Memory Cards, Memory Submodules, Interface Submodules
Содержание S5-135U
Страница 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Страница 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Страница 26: ...2 8 SystemManual C79000 G8576 C199 06 Centralized and Distributed Configuration of a Programmable Controller ...
Страница 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Страница 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Страница 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Страница 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...