![Siemens S5-135U Скачать руководство пользователя страница 478](http://html.mh-extra.com/html/siemens/s5-135u/s5-135u_system-manual_377341478.webp)
9-96
System Manual
C79000-G8576-C199-06
Operational error limit (0
o
C ... 60
o
C)
– voltage ranges except for 0-1.25 V,
$
1.25 V
– current ranges and 0-1.25 V,
$
1.25 V
0.2 %
0.2 %
Error signal
for overflow
for internal error
Yes (overflow bit set)
Yes (error bit (= E bit) set)
Single error
linearity
tolerance
polarity reversal error
0.02 %
0.05 %
0.05 %
Temperature error
0.005 %/K
Insulation rating
To VDE 0160
Line length
- shielded
200 m max.
Front connector
43-way
Power dissipation of module
3.5 W typical
Weight
Approx. 0.4 kg
Rated insulation voltage
(between channels and ground point) tested at
500 V
Analog Input/Output Modules