![Siemens S5-135U Скачать руководство пользователя страница 472](http://html.mh-extra.com/html/siemens/s5-135u/s5-135u_system-manual_377341472.webp)
9-90
System Manual
C79000-G8576-C199-06
The channels have the following designations on the module:
Channel 0:
M0 +
M0 –
Channel 1:
M1 +
M1 –
:
:
Channel 7:
M7 +
M7 –
Channels are arranged in groups of four, for which you can set separate
measuring ranges:
Channel group I:
Channels 0 to 3
Channel group II: Channels 4 to 7
The following figure shows the connection of sensors to the module.
You must observe the following condition:
U
E
+ U
CM
< 12 V
(i.e. the sum of the set voltage range and common-mode voltage must be less
than 12 V; current measuring ranges correspond to a voltage of 2.5 V).
M+
M–
M+
U
ISO
MUX
0 V Bus
+
–
+
–
U
E2
U
CM2
+
–
+
–
U
CM1
M–
0 V
ext
U
E1
Analog Input Module
U E1/2: Input Voltage
U ISO: Potential Difference
: Equipotential; this potential is established by the sensor reference potential
(external reference potential)
U CM1/2: Common-Mode Voltage
Figure 9-31
Connecting Sensors to the 466 Analog Input Module (Differential Measurement)
Analog Input/Output Modules
Содержание S5-135U
Страница 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Страница 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Страница 26: ...2 8 SystemManual C79000 G8576 C199 06 Centralized and Distributed Configuration of a Programmable Controller ...
Страница 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Страница 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Страница 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Страница 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...