6-11
System Manual
C79000-G8576-C199-06
Executing a RESET at all CPUs:
Action
Reaction
Execute a RESET at each individual
CPU:
Hold the MC
1)
mode switch at the
RESET setting; simultaneously set the
mode switch from STOP to RUN.
The red STOP LED on each CPU
is continuously lit; each CPU
emits the output inhibit signal.
The CPUs are in the wait state.
1)
MC: Momentary-contact
Symptom 1:
The STOP LED of one CPU flashes slowly. When the control bits of this
CPU are read out with the programmer, “DB 1 error” is marked in addition to
the usual information. There is no output of an ISTACK.
Remedy:
Check whether data block DB1 in the CPU was correctly loaded and
programmed.
Symptom 2:
After execution of a RESET:
Undefined states or faults occur at the CPUs (e.g. after a RESTART at
CPU 922, it goes to the RUN state although the other CPUs are still at
STOP).
Remedy:
Verify the following points:
Is the coordinator inserted?
Are all modules correctly inserted (engaged)?
Are all modules at the correct slots?
Step 7
Possible Faults
Multiprocessor Operation/Coordinators
Содержание S5-135U
Страница 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Страница 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Страница 26: ...2 8 SystemManual C79000 G8576 C199 06 Centralized and Distributed Configuration of a Programmable Controller ...
Страница 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Страница 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Страница 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Страница 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...