9-71
System Manual
C79000-G8576-C199-06
Measuring range 500 mV; card with 31.25 ohm shunt
(6ES5 498-1AA51/AA71)
The 4 to 20 mA range is resolved to 2048 units at an interval of 512 to 2560.
If you require a representation from 0 to 2048, you must subtract 512 units by
software. Please note the following:
A broken wire signal cannot be emitted.
Detection of the overrange can be achieved by scanning bits 2
9
and 2
11
.
A broken wire can be detected with currents < 3 mA.
If you short-circuit the positive and negative terminals of the transducer
when using the 6ES5 498-1AA51 range card (for a two-wire transducer),
the current is limited to about 28 mA. Until the thermal current limiting
circuit responds in the range card (about 3 s), a short-circuit current of
approximately 250 mA flows; this sets the overflow bit for this duration
at all channels.
Units
Input Cur-
t i
A
Byte 0
Byte 1
rent in mA
7
S
6
2
11
5
2
10
4
2
9
3
2
8
2
2
7
1
2
6
0
2
5
7
2
4
6
2
3
5
2
2
4
2
1
3
2
0
2
A
1
E
0
OV
w
4096
w
32.000
0
1
1
1 1 1 1 1 1 1 1 1 1 0/1
0 1
Overflow
4095
3072
3071
2561
31.992
24.0
23.992
20.008
0
0
0
0
1
1
1
1
1
1
0
0
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
0/1
0/1
0/1
0/1
0
0
0
0
0
0
0
0
Overrange
Short-circuit with two-
wire transducer
2560
2048
512
20.0
16.0
4.0
0
0
0
1
1
0
0
0
0
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0/1
0/1
0/1
0
0
0
0
0
0
Rated range
511
384
383
3.992
3.0
2.992
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
0
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
0/1
0/1
0/1
0
0
0
0
0
0
Range
underflow
0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0/1
0 0
Broken wire
A = Active bit
E = Error bit
OV = Overflow bit
S = Sign
Measured-Value
Representation for
Current Measuring
Ranges from 4 to
20 mA
Current Limiting
Analog Input/Output Modules
Содержание S5-135U
Страница 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Страница 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Страница 26: ...2 8 SystemManual C79000 G8576 C199 06 Centralized and Distributed Configuration of a Programmable Controller ...
Страница 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Страница 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Страница 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Страница 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...