5-23
System Manual
C79000-G8576-C199-06
Given in the following overview are the causes for LEDs lighting up:
QVZ LED
on
A module addressed by the program no longer acknowledges
although/because
it either acknowledged in single-processor operation upon
restart of the CPU 948 in the area of the process image
(IB0 to 127, QB0 to 127) and has been entered as present
in the so-called 9th track;
or it has been entered in multi or single-processor
operation in DB 1 (address list) and has been recognized
as present during the restart;
or it was addressed in direct access by operations LPY,
LPW, TPY, TPW, LOY, LOW, TOY, TOW;
or the data handling blocks cannot access the module.
Possible causes:
Module failure
Module removed during operation, in the STOP state or in
the Off state without subsequent restart.
A timeout occurred during access to the user memory.
ADF LED
on
The user program has referred to an address in the process
image under which no module was inserted in the I/Os or was
not entered in DB 1 during the last restart.
ZYK LED
on
The preset cycle time monitor has responded and cyclic
program processing is interrupted.
BASP LED
on
Command output is inhibited and the digital outputs will be
directly switched to the safe state (0).
INIT LED
on
This LED is continuously lit for a short time during
initialization after power ON and during operation in the
event of system faults.
A detailed description of interrupt and error handling can be found in the
CPU 948 Programming Guide.
LEDs for Fault
Indication and
Signaling
CPUs, Memory Cards, Memory Submodules, Interface Submodules
Содержание S5-135U
Страница 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Страница 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Страница 26: ...2 8 SystemManual C79000 G8576 C199 06 Centralized and Distributed Configuration of a Programmable Controller ...
Страница 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Страница 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Страница 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Страница 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...