18/46
Siemens
Heating controllers RVP201 and RVP211
CE1P2464en
Building Technologies
3 Technical design
2017-07-21
3.3.5 Generation of setpoint
The setpoint is generated via the heating curve based on the
composite
outside tem-
perature.
2
4
6
2B
0
2
H
T
Vw
T
Rw
T
AM
0
0
-
s
Generation of setpoint with weather-compensated control, without a room unit
H
Heating curve
s
Slope of heating curve
T
AM
Composite outside temperature
T
Rw
Room temperature setpoint
T
Vw
Flow temperature setpoint
2
4
64
B
0
2
E
H
T
Vw
T
Rw
+10 K
-10 K
I
+20 K
-20 K
L
T
Rx
1
/
2
1
s
s
0
0
-
×
×
×
T
AM
Generation of setpoint with weather-compensated control, with authority of room tem-
perature deviation
×
Multiplier
E
Authority (gain factor) of room temperature deviation
H
Heating curve
I
Integrator with limitation
L
Limiter
s
Slope of heating curve
T
AM
Composite outside temperature
T
Rw
Room temperature stepping
T
Rx
Room temperature
T
Vw
Flow temperature setpoint
The setpoint is generated based on the setpoint / actual value deviation of the room
temperature.
Also, the heating curve slope with a fixed outside temperature of 0 °C is taken into ac-
count. The generation of this factor corresponds exactly to the generation of the flow
temperature setpoint in the case of weather-compensated control with or without room
temperature influence.
Weather-compensated
control
Without room unit
With authority of room
temperature deviation
Room temperature-
compensated control