Settings on the “Heating engineer” level
Press
and
simultaneously for 3 seconds to activate the “Heating engineer” level for se-
lecting the plant type and the plant-related variables.
Selecting the plant type on operating line 51:
The required plant type must be selected on operating line 51 using buttons
and
This
activates all functions required for the respective type of plant and shows the associated operat-
ing lines.
A plant type is comprised of a space heating circuit (5 different types) and a d.h.w. circuit (4
different types). The 2 types of circuits can be combined in 21 different ways. The following plant
diagrams show all possible combinations.
The controller's operating line 51 only accepts combinations that are possible.
Example of a setting:
25
40Z
02
1 = Space heating type 1
2 = d.h.w. circuit type 2
51 Plant
type
2
−
1
(1
−
0 … 5
−
4)
.........................
Type numbers in the following
section
Plant types
A6
Room unit
K6 Electric immersion heater
B1
Flow temperature sensor
M1 Circulating pump / bypass pump
B2
Boiler temperature sensor
M2 Heating circuit pump
B3
Flow temperature sensor for d.h.w.
M3 Charging pump
B31 D.h.w. storage tank temperature sensor / thermostat 1
M4 Boiler pump or circulating pump
B32 D.h.w. storage tank temperature sensor / thermostat 2
M5 Collector pump
B5
Room temperature sensor
N1 Controller RVL482
B6
Collector sensor
U1 Solar sensor
B7
Return temperature sensor
U2 Wind sensor
B9
Outside sensor
Y1 Heating circuit mixing valve
E1
Heat source (boiler)
E2 Consumer
(space)
LPB Data
bus
Y7 D.h.w. mixing valve or mixing valve for minimum
limitation of the boiler return temperature