Building Technologies
74 319 0619 0 a
17.04.2008
64/288
en
195 Controller's soft-
ware version
Display function
196 Identification
code
of room unit
Display function
Block “Solar d.h.w.“
201 Temperature
differ-
ential ON solar
8 °C
(0…40)
...................
°C
Temperature differential be-
tween collector and storage
tank
202 Temperature
differ-
ential OFF solar
4 °C
(0…40)
...................
°C
Temperature differential be-
tween collector and storage
tank
203 Collector frost pro-
tection
--- °C
(--- / –20…5)
...................
°C
Setting --- = No collector frost
protection
204 Collector over tem-
perature protection
105 °C
(--- / 30…260)
...................
°C
Setting --- = No collector over
temperature protection
205 Evaporation heat
carrier
140 °C
(--- / 60…260)
...................
°C
Setting --- = No collector pump
protection
206 D.h.w. charging
temperature maxi-
mum limitation
80 °C
(8…100)
...................
°C
207 D.h.w. storage tank
temperature maxi-
mum limitation
90 °C
(8…100)
...................
°C
No safety function
208 Collector start func-
tion gradient
--- min/°C
(--- / 1…20)
...........
min/°C
Setting --- = Function deacti-
vated