86 P-band of control
(Xp)
32.0 °C
(1.0…100.0)
...................
°C
87 Integral action time
of control (Tn)
120 s
(10…873)
......................
s
Block “Boiler”
91 Boiler
operating
mode
0
(0…2)
.........................
0 = with manual shutdown
( key)
1 = with automatic shutdown
(OFF when there is no
demand for heat)
2 = without shutdown
92 Maximum
limitation
of boiler temperature
95 °C
(25…140)
...................
°C
No safety function
93 Minimum
limitation
of boiler temperature
10 °C
(5…140)
...................
°C
94 Switching
differential
of boiler
6 °C
(1…20)
...................
°C
95 Minimum
limitation
of burner running
time
4 min
(0…10)
................
min
96 Release limit for
second burner stage
50
°C×min
(0…500)
..........
°C×min
97 Reset limit for sec-
ond burner stage
10
°C×min
(0…500)
..........
°C×min
98 Waiting time for
second burner stage
20 min
(0…40)
................
min
Block “Pump M1”
99 Operating mode
pump M1
1
(0…3)
.........................
0 = circulating pump without
shutdown in the case of pro-
tective boiler startup
1 = circulating pump with shut-
down in the case of protec-
tive boiler startup