Block "3-position actuator for d.h.w. / mixing circuit"
108 Actuator running
time
120 s
(30…873)
......................
s
109 P-band of control
(Xp)
32.0 °C
(1.0…100.0)
...................
°C
110 Integral action time
of control (Tn)
120 s
(10…873)
......................
s
Block "Integral action time of maximum limitation of return temperature"
114 Integral action time
of maximum limita-
tion of return tem-
perature
30 min
(0…60)
................
min
Block “Assignment of d.h.w. heating”
121 Assignment
of
d.h.w. heating
0
(0…2)
.........................
D.h.w. heating for
0 = own controller
1 = all controllers in the inter-
connected system that use
the same segment number
2 = all controllers in the inter-
connected system
Block “Circulating pump”
122 Program for d.h.w.
circulating pump
2
(0…3)
.........................
0 = 24 h per day
1 = according to the heating
program(s), depending on
the setting made on line 121
2 = according to switching pro-
gram 2
3 = according to switching pro-
gram 3