Basic Documentation RVL470
Siemens Building Technologies
36/68
Function block "Boiler"
Landis & Staefa Division
If the boiler sets the forced signal to zero, the loads and heat exchanges that have re-
sponded to the forced signal respond as follows:
•
They close the slipper or seat valves
•
Their pumps run for the set pump overrun time and then stop
10.5. Operating mode of pump M1
The operating mode during protective boiler startup of the pump M1 must be selected
on operating line 99:
•
Circulating pump with no deactivation (setting 0):
The circulating pump runs when one of the consumers calls for heat and when burner
stage 1 is switched on, that is, also during protective boiler startup.
•
Circulating pump with deactivation (setting 1):
The circulating pump runs when one of the consumers calls for heat. It is deactivated
during protective boiler startup.