13.2. Display functions
13.2.1. Flow temperature setpoint
Displayed is the current flow temperature setpoint which is composed of the following
variables:
•
Flow temperature setpoint in function of the composite outside temperature and the
heating curve
•
Position of the setting knob for room temperature readjustments
•
Parallel displacement of heating curve (setting on operating line 72)
With demand-compensated control (plant types 4, 5 and 6), the display shows --- .
Generation of flow temperature setpoint:
T
AM
, composite
outside
temperature
Knob on
controller
Flow temperature setpoint
operating line 165
1 + s
Parallel displacement of
heating curve, operating line 72
1 + s
25
22
B
1
0
e
T
V
T
AM
T
VS
Heating curve
T
V
T
VS
s
s
Slope
T
AM
Composite outside temperature
T
VS
Flow temperature setpoint (generated via the heating curve)
T
V
Flow temperature setpoint