Siemens Building Technologies
Basic Documentation RVL470
CE1P2522E / 30.03.2000
Landis & Staefa Division
Function block "End-user 1"
13/68
5. Function block "End-user 1"
This function block contains settings that the end-user himself can make.
5.1. Operating lines
Line
Function, parameter
Unit
Factory
setting
Range
1
Setpoint for NORMAL heating
°C
20.0
0...35
2
Setpoint for REDUCED heating
°C
14.0
0...35
3
Setpoint for frost protection / holiday mode
°C
10.0
0...35
4
Weekday
1-7
1...7, 1-7
5
1st heating period, start of NORMAL heating
hh:mm
06:00
--:-- / 00:00...24:00
6
1st heating period, start of REDUCED heating
hh:mm
22:00
--:-- / 00:00...24:00
7
2nd heating period, start of NORMAL heating
hh:mm
--:--
--:-- / 00:00...24:00
8
2nd heating period, start of REDUCED heating
hh:mm
--:--
--:-- / 00:00...24:00
9
3rd heating period, start of NORMAL heating
hh:mm
--:--
--:-- / 00:00...24:00
10
3rd heating period, start of REDUCED heating
hh:mm
--:--
--:-- / 00:00...24:00
11
Holiday period 1...8
1...8
12
Date of first day of holidays
dd:MM
--:--
00.00. ... 31.12.
13
Date of last day of holidays
dd:MM
--:--
00.00. ... 31.12.
14
Heating curve, flow setpoint TV1 at 15 °C outside
temperature
°C
30
20...70
15
Heating curve, flow setpoint TV2 at –5 °C outside
temperature
°C
60
20...120
5.2. Setpoints
5.2.1. General
The setpoint of the NORMAL and the REDUCED temperature and of frost protection for
the plant / holiday mode are entered directly in °C room temperature. They are inde-
pendent of whether or not the control uses a room temperature sensor.
5.2.2. Frost protection for the building
The lowest valid room temperature setpoint always corresponds to at least the setpoint
of frost protection / holiday mode (setting on operating line 3), even if lower values have
been entered as the setpoints of the NORMAL and the REDUCED temperature (set-
tings on operating lines 1 and 2).
If a room temperature sensor is used and the room temperature falls below the holiday /
frost protection setpoint, ECO – if available – will stop OFF until the room temperature
has risen 1 °C above the holiday / frost protection setpoint.
5.3. Heating program
The heating program of the RVL470 provides a maximum of three heating periods per
day. Also, every weekday may have different heating periods.
Note:
The entries to be made are not switching times, but periods of time during which the
NORMAL temperature shall apply. Usually, these periods of time are identical to the
building's occupancy times. The actual switching times for the change from the
REDUCED to the NORMAL temperature, and vice versa, are calculated by the optimi-
zation function, provided it is activated. Using the setting "1-7" on operating line 4, it is
possible to enter a heating program that applies to all days of the week. This simplifies
the settings: if the weekend settings differ from the other weekday settings, first enter