CE1P2522E / 30.03.2000
Basic Documentation RVL470
Siemens Building Technologies
56/68
Communication
Landis & Staefa Division
•
Overriding the operating mode
•
Overriding the room temperature setpoints
•
Readjustment of room temperature
•
Entry of weekday and time of day
•
Overriding the heating program
•
Display of actual values acquired by the RVL470
For this purpose, the QAW70 has the following operating elements:
•
Operating mode button
•
Economy button (also called presence button)
•
Setting knob for room temperature readjustments
•
Buttons for selecting the operating lines
•
Buttons for changing the values
17.1.3.1. Overriding the operating mode
From the QAW70, the operating mode of the RVL470 can be overridden. This is ac-
complished with the operating mode button and the economy button.
To enable the room unit to act on the RVL470, the following operational conditions must
be satisfied on the controller:
•
AUTO mode
•
No holiday period active, no manual operation
The effect of the QAW70's operating mode button on the RVL470 is as follows:
Operating mode
QAW70
Operating mode RVL470
AUTO; temporary overriding with economy button possible
Continuously NORMAL heating or continuously REDUCED
heating, depending on the economy button
Standby
17.1.3.2. Setting knob for room temperature readjustments
With the setting knob of the QAW70, the room temperature setpoint of NORMAL heat-
ing can be readjusted by ±3 °C.
The setting of the room temperature setpoint on the controller's operating line 1 will not
be affected by the QAW70.
17.1.3.3. Effect of the individual QAW70 operating lines on the RVL470
If 1 (slave with no remote adjustment) is entered on operating line 178 (clock mode) of
the RVL470, the time of day on the QAW70 cannot be changed.
Line on
QAW70
Function, parameter
Effect on RVL470, notes
1
Setpoint of NORMAL heating
Changes operating line 1 on the RVL470
2
Setpoint of REDUCED heat-
ing
Changes operating line 2 on the RVL470
3
Setpoint of d.h.w. temperature Not available on the RVL470
4
Weekday (entry of heating
program)
Changes operating line 4 on the RVL470
5
First heating period, start of
NORMAL heating
Changes operating line 5 on the RVL470
6
First heating period, start of
REDUCED heating
Changes operating line 6 on the RVL470