background image

Thank you for purchasing the Mitsubishi general-purpose

programmable controller MELSEC-A series.

Prior to use, please read this manual thoroughly and
familiarize yourself with the product.

z

z

z

z

 SAFETY PRECAUTIONS 

z

z

z

z

(Read these precautions before using.)

When using Mitsubishi equipment, thoroughly read this manual and
the associated manuals introduced in the manual.  Also, pay careful
attention to safety and handle the module properly.

These precautions apply only to Mitsubishi equipment.  Refer to the
CPU module user's manual for a description of the PC system safety
precautions.

These 

z

SAFETY PRECAUTIONS

z

 classify the safety precautions

into two categories: "DANGER" and "CAUTION".

Procedures which may lead to a dangerous
condition and cause death or serious injury if not
carried out properly.

Procedures which may lead to a dangerous
condition and cause superficial to medium
injury, or physical damage only, if not carried out
properly.

Depending on circumstances, procedures indicated by 

CAUTION

may also be linked to serious results.

In any case, it is important to follow the directions for usage.

Store this manual in a safe place so that you can take it out and read
it whenever necessary.  Always forward it to the end user.

[Design precautions]

 DANGER

z

 Configure a safety circuit external to the PC, so that the entire

system operates safety even if there is an external power error or if
the PC is malfunctioning.

[Design precautions]

CAUTION

z

 Do not bundle, or near the control cables and communication cables with

the main circuit and power cables.  Keep them at least 100mm
(3.94inch) away from such cables.  Noise may cause malfunction.

[Installation precautions]

CAUTION

z

 Use the PC in the environment given in the general specifications of the

this manual.  Using the PC outside the range of the general
specifications may result in electric shock, fire or malfunctioning. or may
damage or degrade the module.

z

 Insert the tabs at the bottom of the module into the mounting holes in the

base module before installing the module, and after tightening the
module fixing screws with specified torque. If the connector is not
property installed and tightened. If may result in malfunctioning,  failure
or cause the module to lam out.
Tightening the screws too far may cause damage to the screw and/or the
module, resulting in fall out, short circuit or malfunctions.

z

 Do not directly touch the module’s conductive parts or electronic

components. Doing so could cause malfunction or failure in the module.

z

 Insert the wire breakage detection connector installation screw into the

mounting holes in the module, and after tightening the connector
installation screw with specified toque. If the connector is not property
installed and tightened, it may result in error detetion of wire breakage.

[Wiring precautions]

CAUTION

z

 Be sure to ground the shield wire with a special PC ground of Type III or

above. Not doing so could result in malfunction.

z

 When wiring in the PC, be sure that it is done correctly by checking the

product's rated voltage and the terminal layout.  Connecting a power
supply that is different from the rating or incorrectly wiring the product
could result in fire or failure.

z

 Tighten the terminal screws with specified torque. Loose terminal screws

may cause a short circuit, fire, or malfunction.
Tightening the terminal screws too far may cause damage to the screw
and/or the module, resulting in short circuit, or malfunctions.

z

 Be sure that cuttings, wire chips, or other foreign matter do not enter the

module. Foreign matter may start a fire or cause failure or malfunctions.

z

 Be sure to fix communication cables and power cables leading from the

module by placing them in the duct or clamping them. Cables not placed
in the duct or without clamping may hang or shift, allowing them to be
accidentally pulled, which may result in a module malfunction and cable
damage.

z

 When detaching the communication cable from the module, do not pull

the cable portion. For cables with connectors, hold the connector at the
junction to the module, then detach it. For cables without connectors,
first loosen the screw at the junction, then detach to the  cable. Pulling
the cable portion while it is connected to the module may cause a
malfunction or damage to the module and cable.

[Starting and maintenance precautions]

CAUTION

z

 Do not touch the terminal while the power is on.

It may cause malfunction.

z

 Make sure to switch all phases of the external power supply off before

cleaning or re-tightening the terminal screws.  If you do not switch off the
external power supply, it will cause failure or malfunction of the module.

z

 Never disassemble or modify the module. This may cause failure,

malfunctioning, injury and/or fire.

z

 Make sure to switch all phases of the external power supply off before

mounting or removing the module.  If you do not switch off the external
power supply, it will cause failure or malfunction of the module.

[Disposal precaution]

CAUTION

z

 When disposing of this product, handle it as industrial waste.

About This Manual

The following product manuals are available.  Please use this table as
a reference to request the appropriate manual as necessary.

Detailed manual

Manual name

Manual No.

(Model Code)

A1S62TCTT-S2 Heating-Cooling Temperature Control Module
A1S62TCTTBW-S2 Heating-Cooling Temperature Control
Module with Wire Breakage Detection Function User's Manual

SH-3643
(13JL35)

Please read A1S62TCTT-S2 Heating-Cooling Temperature Control Module
A1S62TCTTBW-S2 Heating-Cooling Temperature Control Module with Wire
Breakage Detection Function User's Manual (Detailed edition) when using this unit.

DANGER

CAUTION

A1S62TCTT-S2 Heating-Cooling

Temperature Control Module

A1S62TCTTBW-S2 Heating-Cooling

Temperature Control Module with Wire

Breakage Detection Function

Mitsubishi General-Purpose Programmable Controller

User’s Manual

(Hardware)

 C  1997 MITSUBISHI ELECTRIC CORPORATION

Type

A1S62TCTT-U-HW-E

Type

Code

13JL32

IB(NA)-66800-C(0210)MEE

Содержание A1S62TCTT-S2

Страница 1: ...ype III or above Not doing so could result in malfunction z When wiring in the PC be sure that it is done correctly by checking the product s rated voltage and the terminal layout Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or failure z Tighten the terminal screws with specified torque Loose terminal screws may cause a short ci...

Страница 2: ...A CTL 6 P H 0 00 to 20 00A Former model CTL 6 P is also applicable Input method Multiplex method A D conversion Heater wire breakage disconnection specification Number of alert delays 3 to 255 I O occupied points Special 32 points Connection terminal 20 points terminal block Supported cable size mm inch 0 75 to 1 5 0 030 to 0 059 Supported solder less terminal R1 25 3 1 25 YS3 RAV1 25 3 V1 25 YS3A...

Страница 3: ...op of the module Remove any foreign matter from the module 4 Tighten the module installation screws within the following tightening torque range Screw position Tightening torque range Module installation screw M4 screw 78 to 118N cm Terminal block terminal screw M3 5 screw 59 to 88N cm Terminal block installation screw M4 screw 78 to 118N cm Wire breakage detection connector installation screw M2 ...

Страница 4: ... Rep Com e Assessoria Tecnica Ltda Av Rio Branco 123 15 and S 1507 Rio de Janeiro RJ CEP 20040 005 Brazil Tel 55 21 221 8343 Germany Mitsubishi Electric Europe B V German Branch Gothaer Strasse 8 D 40880 Ratingen GERMANY Tel 49 2102 486 0 U K Mitsubishi Electric Europe B V UK Branch Travellers Lane Hatfield Herts AL10 8XB UK Tel 44 1707 276100 Italy Mitsubishi Electric Europe B V Italian Branch Ce...

Отзывы: