BA 5200 EN 08/2010
Avoid burns when working with corrosive cleaning agents. Always observe the
manufacturers’ instructions for safety and use.
Wear personal protective equipment (gloves, safety glasses)!
•
Seriously contaminated cooling coils must be replaced. Consult our Customer Service.
•
Reconnect the water in and outflow pipes.
10.2.8
Check water oil-cooler
•
The instructions in items 5.7.3, 7.2.2 and 10.1 must be observed.
•
Close the stop valves in the coolant in- and outflow pipes.
•
Inspect cooler for leaks in the water conducting piping.
•
Check the condition of screw connections and, if necessary, replace.
10.2.9
Check hose lines
Even when adequately stored and subjected to permissible loads, hoses and hose lines are subject to a
natural ageing process. This limits their period of use.
The period of use of the hose lines must not exceed 6 years from the manufacturing
date stamped on them.
The period of use can be determined using available test and empirical values, taking into account the
conditions of use.
The operator of the system must ensure that hose lines are replaced at suitable intervals of
time, even if no defects which may affect their safe operation are identifiable on them.
Hose lines must be inspected for safe working condition by an expert before the plant is first
put into operation and thereafter at least once a year.
If during inspections faults are found, these must be rectified immediately or suitable
countermeasures taken.
10.2.10 Top up oil
•
The instructions in item 7.1 must be observed!
•
Always top up with the same type of oil as already used in the unit (see also item 10.2.2).
10.2.11 Check tightness of fastening bolts
•
The instructions in item 10.1 must be observed!
•
Check tightness of all fastening bolts.
Damaged bolts must be replaced with new bolts of the same type and strength class.