58/70
Siemens Building Technologies
Basic Documentation QAA73.110 Room unit
CE1P2284en
HVAC Products
Description
of the OEM settings
10.07.2002
Service functions OEM
5.11 Info display
The Info display can be made to appear continuously or temporarily.
1. Press the line selection buttons to select line 150.
2. Press the + / - buttons to select the display mode.
Setting range
Unit
Factory setting
Temporary, continuously
–
Temporary
This setting selects the display mode of the Info display:
When entering X:
Temporary
The information selected on the Info level is displayed for only 8
minutes. After that period of time, the display will return to the standard
display (actual room temperature, time of day and time pointer)
Continuously The information selected last with the Info button will be continuously
displayed.
5.12 Frost warning
A frost warning can be generated depending on a selectable outside temperature.
1. Press the line selection buttons to select line
151
.
2. Press the + / – buttons to select the required function.
Setting range
Unit
Factory setting
– – . – / –10 ... +10
°C
3.0
– – . – no frost warning
If the outside temperature falls to the selected temperature level or drops below it, the
Info display shows the actual outside temperature as a flashing value.
Description
Line 150
Effect
Description
Line 151
Note
Effect