28/70
Siemens Building Technologies
Basic Documentation QAA73.110 Room unit
CE1P2284en
HVAC Products
Description
of enduser settings
10.07.2002
Time switch programs TSP1 and TSP2 and d.h.w.
For the 2 heating circuits 1 and 2 as well as for d.h.w., it is possible to define
independent time switch programs. This serves the following purpose:
•
Space heating and d.h.w. heating operate only if there is a demand for heat
•
The user can set the occupancy times to suit his lifestyle
•
Energy can be saved by making adequate use of the time switch programs
For TSP1, parameters 10 through 16 are provided, für TSP2, the parameters 20
through 26 and for TSP3 the parameters 30 through 36.
•
The time switch programs operate independently of each other.
•
Die Parameter 20 ... Parameters 20 through 26 are visible only if boiler control
supports a second heating circuit
•
Die Parameter 30 ... Parameters 30 through 36 are visible only if line 91 is set for
use by the d.h.w. time switch program
3.10 Preselecting the weekday
With this setting, you select the weekdays or the 7-day block for which the switching
times of the time switch program apply.
1. Press the line selection buttons to select line
10
or
20
or
30
.
2. Press the + / – buttons to preselect the 7-day block or the individual day.
Setting range
Unit
Week Mo...Su
7-day block
Individual days
•
This setting must be made before the switching times are entered!
•
For every day on which other switching times shall apply, the preselection of the
individual day with subsequent entry of the switching times must be repeated
This setting is used to select either the whole week or individual days.
7-day block:
Entry of the switching times on lines 11 through 16 (for HC1), or of lines 21 through 26
(for HC2), or of lines 31 through 36 (for HC3), is identical for every day from Monday
through Sunday
Example of a time switch program valid for all weekdays
0
2
4
6
8
10
12
14
16
18
20
22
24 h
Mo
...
So
22
84Z18
11
12
Description
Notes
Description
Zeilen 10, 20, 30
Important
Effect
Entry of 7-day block