15/70
Siemens Building Technologies
Basic Documentation QAA73.110 Room unit
CE1P2284en
HVAC Products
Handling
10.07.2002
2.6.1
Overview of enduser parameters
Line
Function
Range
Unit
Resolution
Factory
setting
Time of day
1
Time of day
0 ... 23:59
hh:mm
1 min
–
2
Date (day, month)
1. Jan ... 31. Dec
dd.mm
1 day
–
3
Year
2000 ... 2094
jjjj
1 year
–
Setpoints
5
Reduced room temperature setpoint (TRRw)
TRF ... TRN
°C
0.5
16.0
6
Frost protection setpoint of room temperature
(TRF)
4 ... TRRw
°C
0.5
10.0
7*
Nominal setpoint of the d.h.w. temperature
(TBWw)
TBWR ... TBWmax
°C
1
55
Time switch program 1 (heating circuit 1)
10
Preselecting the weekday
Mo...Su, week
week-
day
1 day
–
11
Switch-on time period 1
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
06:00
12
Switch-off time period 1
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
22:00
13
Switch-on time period 2
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
14
Switch-on time period 2
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
15
Switch-on time period 3
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
16
Switch-off time period 3
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
Time switch program 2
20*
Preselecting the weekday
Mo...Su, week
week-
day
1 day
–
21*
Switch-on time period 1
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
06:00
22*
Switch-off time period 1
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
22:00
23*
Switch-on time period 2
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
24*
Switch-off time period 2
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
25*
Switch-on time period 3
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
26*
Switch-off time period 3
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
Time switch program 3 (d.h.w.)
30*
Preselecting the weekday
Mo...Su, week
week-
day
1 day
–
31*
Switch-on time period 1
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
06:00
32*
Switch-off time period 1
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
22:00
33*
Switch-on time period 2
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
34*
Switch-off time period 2
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
35*
Switch-on time period 3
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
36*
Switch-off time period 3
– – : – –
/ 00:00 ... 24:00
hh:mm
10 min
– – : – –
Holidays
40
Holidays start (day.month) – –
Inactive
1. Jan ... 31. Dec
dd.mm
1 day
– – : – –
41
Holidays end (day.month) – –:
Inactive
1. Jan ... 31. Dec
dd.mm
1 day
– – : – –
42
Heating circuit operating level during holidays
Frost, reduced
–
–
Frost
General
45
STANDARD time switch programs for HC1 + 2
and d.h.w.
(press both buttons -/+ for 3 s)
No, yes
–
–
No
46
Summer / winter changeover temperature
8 ... 30
°C
0.5
17.0
47
Language
German, English
–
–
German
50*
Display of fault (error code of QAA73.110 or
boiler control)
0 ... 255
–
1
–
* These lines are only displayed in OpenTherm Plus mode. Also, the relevant functions
must be supported by boiler control.
– – : – – =
Switching point inactive