General
3.14 Standard times
The standard time program resets the time settings of all time switch programs. For this
purpose, the room unit is supplied with non-volatile factory settings.
1. Press the line selection buttons to select line 45.
2. Press the + / – buttons for 3 seconds.
The standard time program is activated as soon as the display changes to ”Yes”.
Display
Unit
No / yes
–
In that case, the individual settings will be lost!
The time settings for the time switch programs will be overwritten with standard values.
This applies to the following settings:
•
Switching times of time switch programs 1 and 2
11
...
16
or
21... 26
•
Switching times for d.h.w. program
31
...
36
Switching point
Setting line
TSP1 or 2 d.h.w.
Standard time
Switch-on time period 1
11 or 21
31
06 : 00
Switch-off time period 1
12 or 22
32
22 : 00
Switch-on time period 2
13 or 23
33
– – : – –
Switch-off time period 2
14 or 24
34
– – : – –
Switch-on time period 3
15 or 25
35
– – : – –
Switch-off time period 3
16 or 26
36
– – : – –
– – : Inactive
Description
Line 45
Caution
Effect
Standard values