Parameter mode / PARA
(Continue with <OK> / picture 10)
In this mode, you can enter the setpoint of superheat as well
as the parameters for superheat control, the MOP function,
and the capacity control (if configured), and safety control (if
configured). Control of superheat is accomplished with a PID
controller. Both the MOP function and capacity control use a
PI algorithm.
Picture Function Parameter
Code Adjustable
Range/increment
Settings
Default
Procedure
Setpoint
SP
0...16 K / 0.1 K
0...28.8 °F / 0.1 °F
6.0 K /
10.8 °F
P-band
XP
2...160 K / 1 K
3...288 °F / 1 °F
10 K /
18 °F
Integral action
time
TN
0...600 s / 1 s
30 s
11
∆
T
D-part
D
0...5 / 1
0
Max. increase of
∆
T SP
SMX
Example
see
page 43
0...50 K / 0.1 K
0...90 °F / 0.1 °F
18.0 K /
32.4 °F
External signal
direction
2)
SD
-1 (0 V / 4 mA = max.
cooling cap.)
1 (0 V / 4 mA = min.
cooling cap.)
1
Setpoint
SP
-45...90 °C / 0.1 °C
-49...194 °F / 0.1 °F
6.0 °C /
42.8 °F
P-band
XP
2...160 K / 1 K
3...288 °F / 1 °F
35 K /
63 °F
12 CAP
1)
Integral action
time
TN
0...600 s / 1 s
95 s
Setpoint
SP
-45...35 °C / 0.1 °C
-49...95 °F / 0.1 °F
15.0 °C /
59.0 °F
P-band
XP
2...160 K / 1 K
3...288 °F / 1 °F
5 K /
9 °F
13 MOP
Integral action
time
TN
0...600 s / 1 s
30 s
14
SAFETY
3)
Valve startup
delay time
VD
0…30 s / 1s
0 s
Set
parameter /
value with
+/-
Confirm
with
<OK>
Exit with
<ESC>
36/124
Building Technologies
CPS40
CE1U3372XX / H 74 319 0555 0 a
HVAC Products
22.09.2006
Содержание PolyCool CPS 40
Страница 26: ...26 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 50: ...50 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 74: ...74 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 98: ...98 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...