4 Controller
4.1 Operation
+
-
To operate the controller, use the operating buttons on the
controller front.
•
Press the <OK>
button to enable changes, or
confirm a change.
•
Press the
+/-
button to change the flashing data, or
select the information screen.
•
Press the <ESC>
button to exit out of the current
level and return to the previous one.
A flashing display indicates adjustable data.
4.2 Operating
modes
The controller functions are divided into four operation
modes: regulation, configuration, parameter and
simulation.
You can activate any desired mode by simulataneously
pressing the +/- buttons and holding them for a least five
seconds. Release the buttons when C1 is flashing.
Follow procedures below to access the operation mode, as
appropriate.
Operation modes
Procedures
When C1 is flashing, press <OK> to
confirm.
Configuration mode
Parameter mode
Simulation mode
Select the mode with +/-, and press
<OK> to confirm.
Or, press <ESC> to exit the current
operation level.
After setting all necessary parameters, the controller will by
default display in regulation mode with superheat setpoint,
current value of superheat, and actual opening of the valve.
32/124
Building Technologies
CPS40
CE1U3372XX / H 74 319 0555 0 a
HVAC Products
22.09.2006
Содержание PolyCool CPS 40
Страница 26: ...26 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 50: ...50 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 74: ...74 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 98: ...98 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...