Simulation mode / SIMU
(Continue with <OK> / picture 15)
Picture Function
Parameter
Code
Adjustable
range
Settings
Default
Procedure
16
Manipulated EIV
opening degree
Setpoint *
DC 0...10 V
signal
MAN EIV 0...10 V /
0.1 V
0.0 V
17 EIV
actual
position
feedback to the
manipulated
opening
DC 0…10 V
signal
0…100 %
opening
MAN EIV
EIV
- -
18
Actual value
display
Evaporation
temperature
Suction gas
temperature
TO
TOH
-
-
Set parameter
/ value with +/-
Confirm with
<OK>
Back to
regulation
mode with
<ESC>
Continously press <ESC> to exit
* Caution! At your own risk!
1) In the simulation mode, the monitoring functions are
deactivated if not enabled via D1. Therefore, your plant
could be seriously damaged.
2) In the simulation mode, the monitoring functions can be
deactivated on purpose (through D1). This allows the
plant to be manually operated for about 15 minutes.
39/124
Building Technologies
CPS40
CE1U3372XX / H 74 319 0555 0 a
HVAC Products
22.09.2006
Содержание PolyCool CPS 40
Страница 26: ...26 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 50: ...50 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 74: ...74 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...
Страница 98: ...98 124 Building Technologies CPS40 CE1U3372XX H 74 319 0555 0 a HVAC Products 22 09 2006 ...