76
TUTORBIT
COSMOGAS
6 - USE
Parameter
Description
Access
level
Adjustment
range
Default value
Custom value
3 way valve 1
Heating circuit 1 parameters
Installer
Thermostat name
Customisable circuit name; present if Configuration>Zones>Zone 1 Mode = FixSp-R
T/ Outd Reset-R
T/ Outd
Reset comp-R
T/ FxSp-Comp.R
T
Installer
Type of zone
Type of zone: MIX = Mixed (with 3 way valve), No Mix = direct heating circuit (without 3 way valve)
Installer
Mix...No Mix
Mix
Time to open
3 way valve opening time; present if Configuration>Zones>3 way valve 1>T
ype of Zone=Mix
Installer
2...900
150 s
Time to close
3 way valve closing time; present if Configuration>Zones>3 way valve 1>T
ype of Zone=Mix
Installer
2...900
150 s
Leak alarm
Mixing valve leak alarm. E.g. If the mixing valve breaks and remains open, this alarm will show this
Installer
Check each
Supply temperature inspection frequency
Installer
0...30
10 min
Dif
ferential
Maximum variation allowed in the verification period (at a time when the 3 way valve should be closed and therefore no temperature increases are expected).
Installer
2...15
5 K
Floor Inertia
With regard to the temperature measured by the room sensor
, a calculation is made on the floor
inertia which increases the supply temperature to overcome or give this inertia first. Present only if Configuration>Zones>Zone Mode N = Outd Reset-RS / FixSp-RS
Installer
15...100
60%
Room Comp. Of
fset Heat
Maximum deviation of the temperature calculated in heating, with respect to the calculation due to the floor inertia. Present only if Configuration>Zones>Zone Mode N = Outd Reset-RS / FixSp-RS
Installer
0...20
15K
Room Comp. Of
fset Cool
Maximum deviation of the temperature calculated in cooling, with respect to the calculation due to the floor inertia. Present only if Configuration>Zones>Zone Mode N = Outd Reset-RS / FixSp-RS
Installer
0...20
5K
3 way valve 2
Heating circuit 2 parameters (submenu equal to 3 way vale 1)
Installer
3 way valve 3
Heating circuit 3 parameters (submenu equal to 3 way vale 1)
Installer
3 way valve 4
Heating circuit 4 parameters (submenu equal to 3 way vale 1)
Installer
3 way valve 5
Heating circuit 5 parameters (submenu equal to 3 way vale 1)
Installer
SN Circuit 1
Serial Number of QMX3 room sensor
. Present only if
Configuration>Zones>Zone Mode N = Outd Reset-RS /
FixSp-RS
Installer
Value
Value
Associate SN Circuit 1
Association of the QMX3 room sensor with the circuit. Present only if
Configuration>Zones>Zone Mode N =
Outd Reset-RS / FixSp-RS
Installer
Yes..-
-
Room Unit
Association 1
Parameter indicating whether the association with the SN Circuit n took place or not.
VPresent only if
Configuration>Zones>Zone Mode N = Outd Reset-RS / FixSp-RS
Installer
Performed-Not performed
Not performed
Save & Reset
Each time this menu is changed, you need to save and reset in order to load the changes in the temperature
controller
Installer
Yes...No
No
Modbus
Heat generator Modbus communication parameters
Installer
Slave 1 address
Logical address of the Modbus protocol for the first heat generator
Installer
1...253
1
Slave 2 address
Logical address of the Modbus protocol for the second heat generator
Installer
1...253
2
Slave 3 address
Logical address of the Modbus protocol for the third heat generator
Installer
1...253
3
Slave 4 address
Logical address of the Modbus protocol for the fourth heat generator
Installer
1...253
4
Continued on the next page
Содержание POL955
Страница 31: ...31 TUTORBIT COSMOGAS Figure 4 14 Electrical connection 4 INSTALLATION ...
Страница 33: ...33 TUTORBIT COSMOGAS Figure 4 16 Electrical connections 4 INSTALLATION ...
Страница 35: ...35 TUTORBIT COSMOGAS Figure 4 18 Electrical connections 4 INSTALLATION ...
Страница 37: ...37 TUTORBIT COSMOGAS Figure 4 20 Electrical connection 4 INSTALLATION ...
Страница 39: ...39 TUTORBIT COSMOGAS Figure 4 22 Electrical connection 4 INSTALLATION ...
Страница 41: ...41 TUTORBIT COSMOGAS Figure 4 24 Electrical connection 4 INSTALLATION ...
Страница 43: ...43 TUTORBIT COSMOGAS Figure 4 26 Electrical connection 4 INSTALLATION ...
Страница 45: ...45 TUTORBIT COSMOGAS Figure 4 28 Electrical connection 4 INSTALLATION ...
Страница 47: ...47 TUTORBIT COSMOGAS Figure 4 30 Electrical connection 4 INSTALLATION ...
Страница 49: ...49 TUTORBIT COSMOGAS Figure 4 32 Electrical connection 4 INSTALLATION ...
Страница 51: ...51 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 34 Electrical connection ...
Страница 53: ...53 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 36 Electrical connection ...
Страница 54: ...54 TUTORBIT COSMOGAS 4 INSTALLATION ...
Страница 57: ...57 TUTORBIT COSMOGAS Figure 4 38 Electrical connection 4 INSTALLATION ...
Страница 59: ...59 TUTORBIT COSMOGAS Figure 4 40 Electrical connection 4 INSTALLATION ...
Страница 61: ...61 TUTORBIT COSMOGAS Figure 4 42 Electrical connection 4 INSTALLATION ...
Страница 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...