69
TUTORBIT
COSMOGAS
6 - USE
6.5 - DHW adjustment
To set the DHW, open
Parameters->DHW->DHW setpoint
and set the required temperature
To operate the DHW according to the time programme, set
Parameters->DHW->DHW Action = Automatic
then set the
DHW time programme on the
Parameters->DHW->Timer
Program
menu (see the programme setting instructions in
Section 6.8)
To deactivate the DHW, select
Parameters->DHW->DHW
Action = Off
To adjust the recirculation temperature, open
Parameters-
>DHW->DHW return setp
and set the required temperature.
Adjust the recirculation time programme from the
Parameters-
>DHW->DHW return timer prog.
menu and set the
programme by following the instructions in Section 6.9.
Note! DHW return only functions based on the times set
in this programme
.
6.6 - Heating adjustment
To deactivate or set the heating to zones “n” (intended as “n” of
any of the 5 zones) automatically (operation according to the
time bands) or manually (operation at constant temperature)
set
Parameters-> Zones -> Zone n -> Action = Off or
Automatic or Manual.
If a QMX3 room sensor is present, this
Action
parameter is not
present and the
Off
or
Automatic
action must be performed
directly on the room sensor.
When the
Action
parameter is set in
Manual
, the supply
temperature to Zone “n” is performed on
Parameters-> Zones
-> Heat Supply Setp
.
To adjust the compensation reduction in Zone “n”, edit the
Parameters->Zones->Night setback
.
Select the required outdoor reset for Zone “n” with the
Parameters->Zones->Outdoor reset
control, then set the
curve parameters as shown in Section 4.11.
Set the time programme for heating Zone “n” with the
Parameters->Zones->Timer Program
control, then set the
parameters as shown in Section 6.10.
6.3 - Access profile
The menus on TutorBit can be displayed according to the
access profile:
- User Profile
- Installer Profile
- Factory Profile
The “
User
” profile is displayed directly with the wheel control
(knob) on the front of the TutorBit.
The “
Installer
” profile is accessed by setting password 0300.
The “
Factory
”
profile is accessed by setting a suitable
password.
The various parameters can be profiled as described in
Section 6.13.
To set the password and have an “installer” profile, proceed
as follows (refer to Figure 6-2):
1.- Power the Tutorbit;
2.- Press and hold knob “6” until “
Entry 0---”
is displayed.
Release knob “6”;
3.- Press and release knob “6”. The display will show the first
digit marked with a zero “
0--”
;
4.- Turn knob “6” to edit the value of the selected digit;
5.- Once the required value is reached, press knob “6” again
to confirm the value and move to the next digit;
6.- When the knob is pressed last to confirm, if the password
is correct, the display will return to show the main menu.
7.- Move the cursor to Status and press the knob “6” to access
the navigation menu.
The installer password can be entered from anywhere in the
navigation menu.
To exit the “
Installer
” profile, de-energise and power the
device again or press and hold knob “6” for 2 seconds. When
the screen changes, select
Register off.
6.4 - Browsing through menus
and editing parameters
Browsing through menus
Proceed as follows to browse through the menus:
1.- From the main screen, select
State
and press the knob
“6”. Now you access the main menu;
2.- Turn knob “6” to scroll through the various menus;
3.- When the chosen menu is highlighted, press knob “6” once
to open a sub-menu;
4.- Turn knob “6” again to scroll through the parameters in
the sub-menu;
5.- Press the “Esc” key to go from a sub-menu to a higher
level menu.
Editing a parameter
Proceed as follows to edit a parameter:
1.- Browse through the menus as described in the paragraph
above until the required parameter is displayed;
2.- Press knob “6”: the parameter to be edited will be
highlighted;
3.- Turn knob “6” to edit the value of the highlighted parameter;
4.- press knob “6” to confirm the changed value or press “Esc”
to exit the parameter without saving the change.
ATTENTION!!! For the changes to be effective in the
“Configuration” menu, “Yes” must be selected in relation
to the “Save&Reset” parameter in the changed sub-
menus.
Содержание POL955
Страница 31: ...31 TUTORBIT COSMOGAS Figure 4 14 Electrical connection 4 INSTALLATION ...
Страница 33: ...33 TUTORBIT COSMOGAS Figure 4 16 Electrical connections 4 INSTALLATION ...
Страница 35: ...35 TUTORBIT COSMOGAS Figure 4 18 Electrical connections 4 INSTALLATION ...
Страница 37: ...37 TUTORBIT COSMOGAS Figure 4 20 Electrical connection 4 INSTALLATION ...
Страница 39: ...39 TUTORBIT COSMOGAS Figure 4 22 Electrical connection 4 INSTALLATION ...
Страница 41: ...41 TUTORBIT COSMOGAS Figure 4 24 Electrical connection 4 INSTALLATION ...
Страница 43: ...43 TUTORBIT COSMOGAS Figure 4 26 Electrical connection 4 INSTALLATION ...
Страница 45: ...45 TUTORBIT COSMOGAS Figure 4 28 Electrical connection 4 INSTALLATION ...
Страница 47: ...47 TUTORBIT COSMOGAS Figure 4 30 Electrical connection 4 INSTALLATION ...
Страница 49: ...49 TUTORBIT COSMOGAS Figure 4 32 Electrical connection 4 INSTALLATION ...
Страница 51: ...51 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 34 Electrical connection ...
Страница 53: ...53 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 36 Electrical connection ...
Страница 54: ...54 TUTORBIT COSMOGAS 4 INSTALLATION ...
Страница 57: ...57 TUTORBIT COSMOGAS Figure 4 38 Electrical connection 4 INSTALLATION ...
Страница 59: ...59 TUTORBIT COSMOGAS Figure 4 40 Electrical connection 4 INSTALLATION ...
Страница 61: ...61 TUTORBIT COSMOGAS Figure 4 42 Electrical connection 4 INSTALLATION ...
Страница 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...