70
TUTORBIT
COSMOGAS
6 - USE
6.10 - Heating circuits time setting
For the heating circuits time setting, open the
Parameters-
>Zones->Programme->
menu
Reset=Yes
to reset the time programme set;
Copy=Yes
to copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday
(example);
and the one you want to copy the programme on:
To: Tuesday
(example);
For programming, enter the start and end times of each time
slot.
If there is no room sensor, the selectable time bands are:
Comfort
(on) or
Off
.
If the QMX3 room sensor is present, the selectable time bands
are:
Comfort, Precomfort, Reduced, Protection
whose
corresponding room temperatures are set to
Parameters->
Room unit data n->
If the time slots are different for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the first day,
you can copy the others, as explained above.
Once the time programme is completed, simply activate it by
setting
Parameters->Zone n->Action = Automatic.
6.11 - Cooling circuits time setting
At the first access of the menu
Parameters->Zones->Cool
Timer program
anomalous default times will result. In order to
restore consistent values, select
Reset = Yes
. Then proceed to
fill in the weekly program in the same way as in Section 6.10.
If there is no room sensor, the selectable time bands are:
Comfort
(on) or
Off
.
If the QMX3 room sensor is present, the selectable time bands
are:
Comfort, Precomfort, Reduced, Protection
whose
corresponding room temperatures are set to
Parameters->
Room unit data n->.
6.7 - Cooling adjustmen
To deactivate or set the cooling to zones “n” (intended as “n” of
any of the 5 zones) automatically (operation according to the
time bands) or manually (operation at constant temperature)
set
Parameters-> Zones -> Zone n -> Action = Off or
Automatic or Manual.
If a QMX3 room sensor is present, this
Action
parameter is not
present and the
Off
or
Automatic
action must be performed
directly on the room sensor.
When the
Action
parameter is set in
Manual
, the supply
temperature to Zone “n” is performed on
Parameters-> Zones
-> Cool Supply Setp.
o adjust the compensation reduction in Zone “n”, edit the
Parameters->Zones->Cool Night setback
.
Select the required outdoor reset for Zone “n” with the
Parameters->Zones->Cooling Outdoor reset
control, then
set the curve parameters as shown in Section 4.11.
Set the time programme for heating Zone “n” with the
Parameters->Zones->Cool Timer Program
control, then
set the parameters as shown in Section 6.10.
6.8 - DHW time program
TutorBit is able to set a programme on 3 daily time slots. Open
the
Parameters->DHW->Time Programme->
menu
The menu displays the following parameters, in order:
Reset=Yes
. to reset the time programme;
Copy=Yes
to copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday
(example);
and the one you want to copy the programme on:
To: Tuesday
(example);
For programming, enter the start and end times of each time
slot.
If the time slots are different for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the first day,
you can use the “Copy” command to copy them to the other
days, as explained above.
Once the time programme is completed, simply activate it
by setting
Parameters->DHW->DHW action = Automatic.
6.9 - Timer DHW return
Set the timer DHW return by opening the menu
Parameters-
>DHW->Timer DHW return->.
The menu displays the following parameters, in order:
Reset=Yes
to reset the time programme;
Copy=Yes
o copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday
(example);
and the one you want to copy the programme on:
To: Tuesday
(example);
For programming, enter the start and end times of each time
slot.
If the time slots are different for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the first day,
you can copy the others, as explained above.
Содержание POL955
Страница 31: ...31 TUTORBIT COSMOGAS Figure 4 14 Electrical connection 4 INSTALLATION ...
Страница 33: ...33 TUTORBIT COSMOGAS Figure 4 16 Electrical connections 4 INSTALLATION ...
Страница 35: ...35 TUTORBIT COSMOGAS Figure 4 18 Electrical connections 4 INSTALLATION ...
Страница 37: ...37 TUTORBIT COSMOGAS Figure 4 20 Electrical connection 4 INSTALLATION ...
Страница 39: ...39 TUTORBIT COSMOGAS Figure 4 22 Electrical connection 4 INSTALLATION ...
Страница 41: ...41 TUTORBIT COSMOGAS Figure 4 24 Electrical connection 4 INSTALLATION ...
Страница 43: ...43 TUTORBIT COSMOGAS Figure 4 26 Electrical connection 4 INSTALLATION ...
Страница 45: ...45 TUTORBIT COSMOGAS Figure 4 28 Electrical connection 4 INSTALLATION ...
Страница 47: ...47 TUTORBIT COSMOGAS Figure 4 30 Electrical connection 4 INSTALLATION ...
Страница 49: ...49 TUTORBIT COSMOGAS Figure 4 32 Electrical connection 4 INSTALLATION ...
Страница 51: ...51 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 34 Electrical connection ...
Страница 53: ...53 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 36 Electrical connection ...
Страница 54: ...54 TUTORBIT COSMOGAS 4 INSTALLATION ...
Страница 57: ...57 TUTORBIT COSMOGAS Figure 4 38 Electrical connection 4 INSTALLATION ...