5.
Once the P term value is set to give the control output of the SF 500 consistent
oscillation and the error is at its minimum, turn the pre-feeder off.
6.
The
I
term value can now be set. Begin by entering the default value of 0.2.
7.
Restart the pre-feeder (test weights or chains still applied) and feed rate setpoint
entered.
8.
Again observe the oscillation of the control output. Compare results to the figures 4,5
and 6 below.
P term is too high
SETPOINT
SETPOINT
P term is too low
SETPOINT
P term is correctly set