P080 Damping Display
Sets the speed at which the displayed rate readings and outputs (alarm and mA) react to
the change. The higher the damping value, the slower the response is. Refer to
Operation
on page 49.
The higher the damping value, the slower the response.
Enter damping value, range 0.000
f
– 999
*Damping is not applicable to the mA output if programmed for PID function (P201 = 2).
P081 Display Scroll Mode
The RUN displays are scrolled either manually by pressing ALT DISP if the scroll mode is
set to OFF, or automatically if the mode is set to on.
Entry:
0 = OFF
f
1 = ON
Relay/Alarm Function (P100 - P117)
These parameters are specific to the use of the relay/alarm function. Refer to
Operation
on page 49.
P100 Relay Function
Sets the relay function for the relay selected, relays 1 to 5 (P100 -01 to -05)
Entry:
0 = OFF
f
1 = rate
2 = diagnostic
3 = PID-01 setpoint deviation*
4 = PID-02 setpoint deviation*
5 = pre-warn
6 = setpoint
τ
7 = on-line calibration**
* valid only if PID system (P400) is enabled.
τ
valid only if batch function (P560) is enabled.
**
valid only if on-line calibration (P355) is enabled.
Note:
The effect of damping (P080-01) on mA output* can be overridden by
mA output damping (P220).