ECO REFERENCE MANUAL
11-6
EG
EXAMPLE 6
LOCAL (KEYPAD)/REMOTE (BMS) SELECTION
A fan is to be speed controlled using a potentiometer to provide the control signal. The
potentiometer value being set either locally, off or remotely via keyswitch selection on the
motor control panel.
All settings based on factory settings with the following exceptions :
PARAMETER CHANGES FROM FACTORY DEFAULTS
SETTING
DESCRIPTION
P053 = 13
TERMINAL 7
SWITCH BETWEEN ANALOG SPEED SETTING AND Eco
KEYPAD SPEED SETTING
P054 =9
TERMINAL 8
SWITCH BETWEEN LOCAL KEYPAD DISPLAY RUN/STOP
AND REMOTE DIGITAL INPUT TERMINAL RUN/STOP
ITEM
DESCRIPTION
A
RUN/STOP COMMAND FROM BMS
B
THREE POSITION KEY SWITCH ON MCC PANEL FOR
LOCAL/OFF/REMOTE SELECTION (SHOWN IN LOCAL
KEYPAD MODE)
C
0 - 10V DC SPEED SETPOINT FROM BMS
5
9
8
7
3
4
2
V
U
W
FUSES
M
A
MICROMASTER Eco
MIDIMASTER Eco
FAULT CONT ACT
CLOSED = HEALTHY
MAIN CONT ACT OR
0-10V DC
C
B
BUILDING MANAGEMENT
SYSTEMS
+
-
(BMS)
MOT OR CONTROL
PANEL
(MCC)
OFF
REMOTE
LOCAL/KEYP AD
DIP SWITCHES
L1
L2
L3
N
PE
L1
20
L2
L3
19
Содержание Micromaster Eco
Страница 1: ......
Страница 49: ...ECO REFERENCE MANUAL 9 8 Frame Size 8 ...
Страница 50: ...ECO REFERENCE MANUAL 9 9 Frame Size 9 ...
Страница 52: ...ECO REFERENCE MANUAL 9 11 Frame Size 6 Frame Size 7 ...
Страница 88: ...ECO REFERENCE MANUAL 12 9 EMC Wiring guidelines to mnimise effects of EMI MICROMASTER Eco Frame size C ...
Страница 148: ...ECO REFERENCE MANUAL 15 17 6SE3290 ODK87 OFB7 Class B EMC Input Filter ...
Страница 183: ......