ECO REFERENCE MANUAL
9-2
The unit must be secured to a suitable, non-combustible, vertical surface (a load bearing wall for the
heavier MIDIMASTER Eco range). Note that the frame size 9 MIDIMASTER Eco units are floor
mounted. Depending on frame size, use nuts, bolts and washers as shown in the following table:
Frame size
A
B
C
4
5
6
7
8
9
Bolt size
M4
M4
M5
M8
M8
M8
M8
M8
M12
Quantity
2
4
4
4
4
4
6
6
up to 15
Torque (Nm)
2.5
2.5
3.0
-
-
-
-
-
-
PP
PP
Use the formula below to calculate the air-
flow required: Air-flow (m
3
/ hr) =
(Dissipated Watts /
∆
T) x 3.1
Typical dissipation (Watts) = 3% of
inverter rating.
∆
T = Allowable temperature rise within
cabinet in °C.
3.1 = Specific heat of air at sea level.
Frame size A units can be DIN rail Mounted.
Frame size 7, 8 & 9 units should be lifted using
lifting lugs provided.
SAFETY INFORMATION AND
ENVIRONMENTAL REQUIREMENTS
•
This equipment must be earthed
•
Do not energise the equipment with the
cover removed
•
The equipment must be installed and
commissioned only by qualified personnel
•
Obey all general and regional installation
and safety regulations relating to work on
high voltage installations, as well as
regulations covering correct use of tools
and personal protective equipment
•
Make sure that the clearance for cooling
inlets and outlets, above and below the
inverter, is at least 150mm. If the unit is
installed in a cabinet, it may be necessary to
install cabinet cooling fans.
•
Use insulated hand tools on mains input
and motor terminals. Dangerous voltages
can be present even when the inverter is
not operating
•
Do not exceed operating temperature range
0°C to 50
°
C for the MICROMASTER Eco,
or 0°C to 40
°
C for the MIDIMASTER Eco
range
•
De-rate the inverter if operating at altitude
above 1000m
•
Do not install the inverter where it will be
subject to shock, vibration, electro-magnetic
radiation, water hazards, or atmospheric
pollutants such as dust or corrosive gasses.
Содержание Micromaster Eco
Страница 1: ......
Страница 49: ...ECO REFERENCE MANUAL 9 8 Frame Size 8 ...
Страница 50: ...ECO REFERENCE MANUAL 9 9 Frame Size 9 ...
Страница 52: ...ECO REFERENCE MANUAL 9 11 Frame Size 6 Frame Size 7 ...
Страница 88: ...ECO REFERENCE MANUAL 12 9 EMC Wiring guidelines to mnimise effects of EMI MICROMASTER Eco Frame size C ...
Страница 148: ...ECO REFERENCE MANUAL 15 17 6SE3290 ODK87 OFB7 Class B EMC Input Filter ...
Страница 183: ......