ECO REFERENCE MANUAL
10-9
CONTROL CONNECTIONS (ALL MODELS)
GENERAL INFORMATION
Use screened cable for the control cable, Class
1 60/75
°
C copper wire only (for UL
compliance). Tightening torque for the field
wiring terminals is 1.1 Nm.
Do not use the internal RS485
connections (terminals 24 and 25) if
you intend using the external RS485
D-type connection on the front panel
(e.g. to connect a Clear Text
Display/option (OPe).
DIP switches select between voltage (V) and
current (I) analogue speed setting inputs. They
also select between either a voltage or current
PID feedback signal. These switches can only
be accessed when:
•
for Frame sizes 4, 5 and 6, the front cover is
removed.
•
for Frame size 7, the lower front cover is
removed.
•
for Frame sizes A, B, C, the flap on the front
cover is open.
MICROMASTER Eco
Insert a small screwdriver in the slot above the
terminal, whilst inserting control wire from
below. Withdraw the screwdriver to secure the
wire.
MIDIMASTER Eco
Control connections to the MIDIMASTER Eco
are made via two terminal blocks located on the
control panel. The terminal blocks are of a two-
part design. The part containing the screw
terminals can be unplugged from its housing
before wires are connected. When all
connections to the terminals have been
secured, the terminal block must be plugged
firmly back into its housing.
Содержание Micromaster Eco
Страница 1: ......
Страница 49: ...ECO REFERENCE MANUAL 9 8 Frame Size 8 ...
Страница 50: ...ECO REFERENCE MANUAL 9 9 Frame Size 9 ...
Страница 52: ...ECO REFERENCE MANUAL 9 11 Frame Size 6 Frame Size 7 ...
Страница 88: ...ECO REFERENCE MANUAL 12 9 EMC Wiring guidelines to mnimise effects of EMI MICROMASTER Eco Frame size C ...
Страница 148: ...ECO REFERENCE MANUAL 15 17 6SE3290 ODK87 OFB7 Class B EMC Input Filter ...
Страница 183: ......