ECO REFERENCE MANUAL
13-13
Parameter
Function
Range
[default]
Description / Notes
Minimum analogue
frequency (Hz)
0 - 150.0
[0.0]
Frequency corresponding to the lowest
analogue input value, i.e.0 V/0 mA or 2 V/4
mA, determined by P023 and the settings of
the DIP selector switches 1, 2 and 3 (
see
the DIP Selector Switches figure in this
section).
This can be set to a higher value
than P022 to give an inverse relationship
between analogue input and frequency
output
(see diagram in P022)
.
Maximum analogue
frequency (Hz)
0 - 150.0
[50.0]
(60)North
America
Frequency corresponding to the highest
analogue input value, i.e.10 V or 20 mA,
determined by P023 and the setting of the
DIP selector switches 1, 2 and 3 (
see the
DIP Selector Switches figure in this section).
This can be set to a lower value than P021
to give an inverse relationship between
analogue input and frequency output. i.e.
f
V/ I
P021
P021
P022
P022
Note: The output frequency is limited by
values entered for P012/P013.
Analogue input 1 type
0 - 2
[0]
Sets analogue input type for analogue input
1, in conjunction with the settings of the DIP
selector switches 1, 2 and 3 (See
see the
DIP Selector Switches figure in this section)
0 = 0 V to 10 V/ 0 to 20 mA Unipolar input
1 = 2 V to 10 V/ 4 to 20 mA Unipolar input
2 = 2 V to 10 V/ 4 to 20 mA Unipolar input
with controlled start/stop when using
analogue input control.
Содержание Micromaster Eco
Страница 1: ......
Страница 49: ...ECO REFERENCE MANUAL 9 8 Frame Size 8 ...
Страница 50: ...ECO REFERENCE MANUAL 9 9 Frame Size 9 ...
Страница 52: ...ECO REFERENCE MANUAL 9 11 Frame Size 6 Frame Size 7 ...
Страница 88: ...ECO REFERENCE MANUAL 12 9 EMC Wiring guidelines to mnimise effects of EMI MICROMASTER Eco Frame size C ...
Страница 148: ...ECO REFERENCE MANUAL 15 17 6SE3290 ODK87 OFB7 Class B EMC Input Filter ...
Страница 183: ......