ECO REFERENCE MANUAL
12-5
EMC
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify compliance of their
apparatus with the EMC directive for the residential, commercial and light industrial environment as
regards the EMC performance characteristics of the power drive system. Performance limits are as
specified in the generic emission and immunity standards EN 50081-1 and EN 50082-1.
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions
EN 55022
Level B1
Conducted Emissions
EN 55022
Level B1
Immunity:
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
1 kV power cables, 0.5 kV control
The MICROMASTER Eco and MIDIMASTER Eco units are intended exclusively for
professional applications. Therefore, they do not fall within the scope of the harmonics
emissions specification EN 61000-3-2.
Содержание Micromaster Eco
Страница 1: ......
Страница 49: ...ECO REFERENCE MANUAL 9 8 Frame Size 8 ...
Страница 50: ...ECO REFERENCE MANUAL 9 9 Frame Size 9 ...
Страница 52: ...ECO REFERENCE MANUAL 9 11 Frame Size 6 Frame Size 7 ...
Страница 88: ...ECO REFERENCE MANUAL 12 9 EMC Wiring guidelines to mnimise effects of EMI MICROMASTER Eco Frame size C ...
Страница 148: ...ECO REFERENCE MANUAL 15 17 6SE3290 ODK87 OFB7 Class B EMC Input Filter ...
Страница 183: ......