128/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
17 PME73.830...
29.11.2011
Value range
Parameter
number
Parameter
Edit
Min.
Max.
Resolution
Factory setting
Password level
reading from level
Password level
writing from level
200
Burner control
224
Specified time air pressure switch
Edit
0 s
13.818 s
0.294 s
13.818 s
SO
OEM
225
Prepurge time -2,1 seconds
Edit
0 s
1237 s
4.851 s
29.106 s
SO
OEM
226
Preignition time
Edit
1.029 s
37.485 s
0.147 s
6.174 s
SO
OEM
230
Interval: End of safety time - fuel valve 1 ON
Edit
3.234 s
74.97 s
0.294 s
9.408 s
SO
OEM
231
Interval: Fuel valve 1 ON - pilot valve OFF
Edit
0 s
74.97 s
0.294 s
2.646 s
SO
OEM
232
Interval: Pilot valve OFF - load controller release
Edit
2.058 s
74.97 s
0.294 s
8.820 s
SO
OEM
234
Postpurge time
Edit
0 s
1237 s
4.851 s
19.404 s
SO
OEM
240
Repetition in the event of loss of flame during operation
0 = none
1 = none
2 = 1 x Repetition
Edit 0
2 1 0
SO
OEM
241.00 Valve
proving
0 = OFF
1 = ON
Edit 0
1 1 1
SO
OEM
241.01 Valve
proving
0 = during prepurge time
1 = during postpurge time
Edit 0
1 1 1
SO
OEM
241.02 Valve
proving
0 = according to P241.01
1 = during prepurge time and postpurge time
Edit 0
1 1 0
SO
OEM
242
Valve proving test space evacuating
Edit
0 s
2.648 s
0.147 s
2.648 s
SO
OEM
243
Valve proving time test atmospheric pressure
Edit
1.029 s
37.485 s
0.147 s
10.290 s
SO
OEM
244
Valve proving test space filling
Edit
0 s
2.648 s
0.147 s
2.648 s
SO
OEM
245
Valve proving time test gas pressure
Edit
1.029 s
37.485 s
0.147 s
10.290 s
SO
OEM
247
Continuous pilot (during operation)
0 = OFF
1 = ON
Edit 0
1 1 0
SO
OEM
257
Postignition time -0.3 seconds
Edit
0 s
13.23 s
0.147 s
2.205 s
SO
OEM
259
Opening time of actuator (timeout)
Edit
0 s
1237 s
4.851 s
300.762 s
SO
OEM
260
Closing time of actuator (timeout)
Edit
0 s
1237 s
4.851 s
300.762 s
SO
OEM
515
Actuator position during prepurge time and postpurge time
0: Purging in low-fire
1: Purging in high-fire
Edit 0
1 1 1
SO
OEM