112/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
16 PME73.820...
29.11.2011
16.4 Connection diagram for LME73.000... without
actuator SQM4...
Note:
The connection diagram shown is merely an example which must be verified in the individual case
depending on the application!
PME73.820... 1-stage
Without
actuator
With/without
valve
proving
X2-09
SA
-Z
SA
-K
L
SA-
N
L
SA
-R
PE
In
p
ut t
o
ca
m
V
2
O
utp
ut
t
o
ca
m
V
2
710
5
d35
e/
1009
Figure 53: Connection diagram for LME73.000... without actuator SQM4...
When using the LME73.000... without actuator according to application
Gas direct
ignition (G), 1-stage, gas direct ignition 1 (G), 1-stage, with valve proving,
wire link
Dbr4 must be fitted to the actuator’s X2-09 as shown above
Parameter P515.01 must be set to 0