194/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
23 Operation via AZL2…
29.11.2011
23.9.2 Parameters
without
index, with no direct display
23.9.2.1.
Example of parameter 224 (specified time air pressure switch) on the
parameter level
P
V
h min s
%
B
ild
172
/1
1
0
7
Press
for specified time for air pressure
signal.
Display: Parameter
224:
blinks, characters
._._
do not.
/reset
P
V
h min s
%
B
ild
173
/1
1
0
7
Press
/reset
for editing mode.
Display:
48.510
Press
or
to shift the former specified
time to change mode one place to the left.
Display: Specified time
48.510
blinks.
or
P
V
h min s
%
B
ild
174
/1
107
Note
To detect display errors, the value appears
one place shifted to the left.
or
P
V
h min s
%
B
ild
175
/1
107
Press
or
to set the specified time.
Display: Specified time
53.361
blinks.