224/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
27 PWM settings
29.11.2011
27.3
PWM safety parameters
Note:
Also see chapter
Initial PWM parameter settings
!
Parameter
Meaning
559
PWM mode control
Determines the behavior of PWM control, delivering a PWM signal proportional to the preset output
(analog/3-position step input).
Control: Controls the PWM speed proportional to the output preset via the analog or 3-position step
input.
Safety mode: Control for defining the PWM safety parameters.
675.00
Minimum PWM with prepurging, SEC
Minimum PWM signal in percent for prepurging
675.01
Maximum PWM with ignition load, SEC
Maximum PWM signal in percent for ignition load
920
(Current) PWM signal fan
PWM signal in percent.
Readable on the service level with AZL2... (press Info button for >3 seconds).